Rack Remote Power NBB-1600CE-D16 :Dual 16-Amp Input, 230V AC, 16-Outlets, IEC320-C13 (Model:NBB-1600CE-D16 )

Rack Remote Power NBB-1600CE-D16 :Dual 16-Amp Input, 230V AC, 16-Outlets, IEC320-C13 (Model:NBB-1600CE-D16 )

Rack Remote Power NBB-1600CE-D16 :Dual 16-Amp Input, 230V AC, 16-Outlets, IEC320-C13 (Model:NBB-1600CE-D16 )

NBB-1600CE-D16
  • Overview
  • Download
Product Discontinued. Contact us at Info@iTechLCD.com for Replace items.

NBB Series Network Boot Bars for Remote Power Management (Vertical)
Servers, routers, and other electronic equipment sometimes "lock-up," often requiring a service call to a remote site just to flip the power switch to perform a simple reboot. NBB-Series Remote Power Management Switches give you the ability to perform this function from anywhere; just point your browser to the IP address of any IPS-Series unit, enter the secure user name and password, and you're just a click away from remote power On, Off or Reboot!
 
 
Model Output Receptacles Voltage Dual Output Total Output Input Power Cords Input Panel Regulatory
NBB-1600 (16)NEMA 5-15R 120V 15 Amps 30 Amps (2) Included IEC320-C14 UL
NBB-1600-D20 (16)NEMA 5-15R 120V 20 Amps 40 Amps $50/Set IEC320-C20 UL
NBB-1600E-D20 (16)IEC320-C13 208V 20 Amps 40 Amps $50/Set IEC320-C20 UL
NBB-1600-CE (16)IEC320-C13 230V 10 Amps 20 Amps N/A IEC320-C14 CE
NBB-1600CE-D16 (16)IEC320-C13 230V 16 Amps 32 Amps N/A IEC320-C20 CE
Two Convenient User Interfaces
The IPS provides two convenient methods for accessing configuration and switching functions; The Web Browser Interface and the Command Line Interface.

The Web Browser Interface consists of a series of simple, easy-to-use web page menus that allow you to select configuration parameters or initiate switching operations using your TCP/IP network and a JavaScript enabled web browser.

The Command Line Interface is an ASCII menu system, which allows you to configure and operate the IPS via telnet over TCP/IP network, via modem connection or via local PC using a terminal program such as Hyperterminal or TeraTerm.

Security and Co-Location Features
Access to the IPS command mode is password protected to prevent unauthorized users from invoking sensitive switching and configuration functions. Both the Web Browser Interface and Command Line Interface require the user to enter a password before allowing access. Telnet control can be user-defined to a discrete TCP port, or completely turned off to ensure that no unprotected port is present.

The IPS also features two different levels of operational passwords; the System Administrator Level and the User Level. The System Level provides access to all configuration and switching functions, while the User Level is limited to switching functions only. Each outlet can have a unique User Level password, and each user can either be allowed to control all plugs, or restricted to specific plugs selected by the Administrator.

Easy to Configure, Easy to Use
The IPS can be configured via network, via modem, or locally via the serial console port. Easy to master, user-friendly menus and commands let you assign a location name, set system parameters and view plug status. Outlets can be switched on, off, rebooted or set to user-defined default status using plug numbers or names.

Reliability and Support
The IPS is built in the USA and backed by a five year warranty. NetReach products are installed in thousands of network sites world wide. Our customers know they can depend on WTI for superior quality and reliability for their most mission-critical operations.

Features:
  • Dual Power Circuits: Up to 20 Amp Models
    Total Up to 40-Amps Maximum Load
  • 8 or 16 Individual Switched Outlets
  • Web Browser Access for Easy Setup and Operation
  • On / Off / Reboot / Default Switching
  • User-Defined Power-Up Default Status
  • IP Addressed, 10Base-T Interface
  • RS232 Modem / Console Port
  • Network Security Features
  • Power-Up Sequencing
  • Manual Power Control Button
  • Various Input Cable Styles Available - Order Separately
Applications:
  • Control Power on any 120, 208, or 230 VAC Powered Device via Internet, Web Browser, Telnet, Modem or Local Terminal
  • Remote Power Management and Control
  • Reboot Servers, Routers, Web Cams, Firewalls and Other Remote Devices
Power Cords:
Power Input:





Safety Retainers:

 
Technical Specifications            NBB - 1600 1600-D20 1600E-D20 1600-CE 1600CE-D16
Interface Descriptions:
Network Interface:
10Base-T Ethernet, RJ45
Console/Modem Port Interface:
Connectors:
DB-9M, RS232C, (DTE Pinout)
1 1 1 1 1
Coding:
Serial ASCII, 7/8 Bits, No Parity
Power:
Voltage:
120VAC, 100/240VAC, 208/240VAC (50/60Hz)
120V 120V 100/240V 105/240V 100/240V
AC Inputs & Connectors (2):
10 Amps, 15 Amps, 20 Amps, 16 Amps
IEC320-C14, IEC320-C20
(2) 15A
IEC-C14
(2) 20A
IEC-C20
(2) 20A
IEC-C20
(2) 10A
IEC-C14
(2) 16A
IEC-C20
AC Output Total:
20 Amps, 30 Amps, 32 Amps, 40 Amps
30A 40A 40A 20A 32A
AC Output - Receptacles (16):
NEMA 5-15, IEC320-C13
(16)
NEMA 5-15
(16)
NEMA 5-15
(16)
IEC-C13
(16)
IEC-C13
(16)
IEC-C13
AC Output - Per Receptacle:
Amps/Watts
1.875A /
225W
2.5A /
300W
2.5A /
600W
1.25A /
300W
2A /
480W
Physical/Environment:
Dimensions:
43.75" (111.1cm) Length (Zero U Mount)
3.00" (7.6cm) Depth
1.75" (4.5cm) Width
     
Dimensions:
44.5" (113cm) Length (Zero U Mount)
3.00" (7.6cm) Depth
2.125" (5.4cm) Width
   
Weight:
12 lbs. (5.5 Kg) Shipping Weight
Operating Temperature:
32°F to 122°F (0°C to 50°C)
Humidity:
10 to 90% RH
Agency Approvals:
UL, cUL, FCC Class A, RoHS Compliant    
UL, cUL, CE, FCC Class A, RoHS Compliant        